Enable Page
The Enable Page controls access to the other Setup Pages. The setpoint minimum and
maximum values, and the security passwords are also set on the Enable Page.
To access the Enable Page, enter the Setup Mode using a level 2 access code (see
description earlier in this manual). Press the Page key until Enable is displayed. Press
the Menu key. Each parameter can be changed by pressing the Menu key until the
desired parameter is displayed, and then pressing the keys to change the value.
NOTE: Changing the enable to “yes” for each page will allow access to the page in
Level 1 security.
Controls access to Program Page
Controls access to AutoStart
Page
Controls access to PID Page
Controls access to Control Page
Controls access to
Communication Page
Controls access to Real Time
Clock Page
Controls access to Relay Page
Controls access to Test Page
Controls access to Zone
Calibration Page
Controls access to Sensor
Calibration Page
Sets minimum setpoint allowed
-73°C to 759°C (-100°F to 1399°F)
Sets maximum setpoint allowed
-73°C to 760°C (-100°F to 1400°F)
Sets maximum high limit setpoint
allowed*
Sets password for access level 1
Sets password for access level 2
Set to DISABLE to lock out
setpoint and high limit setpoint
changes in Manual and Timer
Modes
* Maximum high limit setpoint = SPUpperLim + HiLimOH
** If the controller does not have this feature, “No” is the only option.