Despatch P1400+ Temperature Controller Manual de usuario Pagina 61

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 110
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 60
55
6. Follow the instructions in the diagram below. At each stage, allow sufficient settling time
before moving on to the next stage.
Table 15.
Manually Tuning Valve Control
Time
Process Variable
T
b
Time
Process Variable
T
a
START
Apply Power to
the load.
Does the
PV
continuously
Oscillate?
Note the time
interval T
a
Set
Pb_P
= 0.8%
Set
ArSt
= T
a
Are the
Oscillations
decaying to
zero?
Multiply
Pb_P
setting by 1.5
END
Note the period
of the decaying
oscillations (T
b
)
Multiply
Pb_P
setting by 1.5
Set
ArSt
= T
b
/2
No
Yes
Yes
No
The controller is now tuned.
Fine-tuning may be required
to optimise the controllers
response
Vista de pagina 60
1 2 ... 56 57 58 59 60 61 62 63 64 65 66 ... 109 110

Comentarios a estos manuales

Sin comentarios